5.1 WALL ENGINEERING

Print this page
View page as PDF

Wall Engineering

There are two main resources for the engineering of flat ICF walls in the United States:

1. PCA 100-2007, Prescriptive Design of Exterior Concrete Walls for One- and Two- Family Dwellings. This document is widely recognized across most of the United States.

The provisions of this Standard apply to the design and construction of concrete footings, foundation walls and above-grade walls, both load bearing and non-load bearing, for:

  1. Detached one and two-family dwellings
  2. Multiple dwellings
  3. One-story buildings of other occupancy groups assigned to Seismic Design Category A.

(This is the first edition of the Portland Cement Association’s (PCA) Prescriptive Design of Exterior Concrete Walls for One- and Two-Family Dwellings. This con - sensus standard was developed by the PCA’s National Standards Development Committee (Committee) that operates under PCA’s American National Standards Institute (ANSI) approved “Procedures for the Development and Maintenance of Portland Cement Association Standards.” The consensus process of PCA for promulgating standards is accredited by ANSI. The Committee is balanced and was formed and operated in accordance with the PCA procedures).

2. ACI 318 “Building Code Requirements for Structural Concrete” is used for walls which are outside the scope and applicability limits of the Prescriptive Method. A local licensed/registered engineer is required to approve the design using this resource.

GREENBLOCK WORLDWIDE CORPORATION, PCA AND ITS MEMBERS MAKE NO EXPRESS OR IMPLIED WARRANTY WITH RESPECT TO THIS PUBLICATION OR ANY INFORMATION CONTAINED HEREIN. IN PARTICULAR, NO WARRANTY IS MADE OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. PCA AND ITS MEMBERS DISCLAIM ANY PRODUCT LIABILITY (IN CLUDING WITHOUT LIMITATION ANY STRICT LIABILITY IN TORT) IN CONNECTION WITH THIS PUBLICATION OR ANY INFORMATION CONTAINED HEREIN.

Table 3.4. Minimum Vertical Reinforcement for
Concrete Crawlspace Walls1,2,3,4,5,6,7,10

Shape of concrete walls Nominal wall thickness8 (in.) Minimum vertical reinforcement – bar size No. and spacing (in.)
Maximum design lateral soil load
30 psf/ft 45 psf/ft 60 psf/ft
Flat 49 4@48 4@38 4@34
6 NR NR NR
8 NR NR NR
10 NR NR NR
Waffle-grid 6 4@48 4@48 4@48
8 NR NR NR
Screen-grid 6 4@48 4@48 4@48
For SI: 1 inch = 25.4 mm; 1 foot = 0.3048 m; 1 psf/ft = 0.1571 kN/m2/m
1 Table values are based on reinforcing bars with a minimum yield strength of 60,000 psi (420 MPa), concrete with a minimum specified compressive strength of 2,500 psi (17.2 MPa), and vertical reinforcement being located at the centerline of the wall. See Section 3.3.
2 Vertical reinforcement with a yield strength of less than 60,000 psi (420 MPa) and/or bars of a different size than specified in the table are permitted in accordance with Section 2.5.7 and Table 2.3.
3 In lieu of using No. 4 bars, No. 3 bars are permitted provided the spacing shown in the table or determined in accordance with Note 2 is reduced by 50%.
4 NR indicates no vertical wall reinforcement is required, except for 6-inch (152 mm) nominal flat walls formed with stay-in-place forming systems in which case vertical reinforcement shall be No. 3@24 (610 mm) or No. 4@48 inches (1219 mm) on center.
5 Applicable only to crawlspace walls 5 feet (1.5 m) or less in unsupported height with a maximum unbalanced backfill height of 4 feet (1.2 m).
6 Interpolation shall not be permitted.
7 Where walls will retain 4 feet (1.2 m) of unbalanced backfill, they shall be laterally supported at the top and bottom before backfilling.
8 Nominal thicknesses are shown for walls. See Table 2.1 for tolerance from nominal thickness permitted for flat walls and thicknesses and dimensions of waffle- and screen-grid walls.
9 Applicable only to one-story construction with floor bearing on top of crawlspace wall.
10 See Sections 3.2.2, 3.2.4 and 3.2.5 for minimum reinforcement required for crawlspace walls supporting above-grade concrete walls.

Table 3.5. Minimum Horizontal Reinforcement for
Concrete Basement Walls1,2

Maximum unsupported height of basement wall-feet (meters) Location of horizontal reinforcement
≤ 8 (2.4) One No. 4 bar within 12 inches (305 mm) of the top of the wall story and one No. 4 bar near mid-height of the wall story
> 8 (2.4) One No. 4 bar within 12 inches (305 mm) of the top of the wall story and one No. 4 bar near third points in the wall story
1 Horizontal reinforcement requirements are for reinforcing bars with a minimum yield strength of 40,000 psi (280 MPa) and concrete with a minimum concrete compressive strength 2,500 psi (17.2 MPa).
2 See Sections 3.2.3, 3.2.4 and 3.2.5 for minimum reinforcement required for basement walls supporting above-grade concrete walls.

Table 3.6. Minimum Vertical Reinforcement for 6-Inch (152 mm)
Nominal Flat Concrete Basement Walls1,2,3,4,5,7,8,9,10

Maximum unsupported wall height (ft) Maximum unbalanced backfill height6 (ft) Minimum vertical reinforcement – bar size No. and spacing (in.)
Maximum design lateral soil load
30 psf/ft 45 psf/ft 60 psf/ft
8 4 NR NR NR
5 NR 5@39 6@48
6 5@39 6@48 6@35
7 6@48 6@34 6@25
8 6@39 6@25 6@19
9 4 NR NR NR
5 NR 5@37 6@48
6 5@36 6@44 6@32
7 6@47 6@30 6@22
8 6@34 6@22 6@16
9 6@27 6@17 DR
10 4 NR NR NR
5 NR 5@35 6@48
6 6@48 6@41 6@30
7 6@43 6@28 6@20
8 6@31 6@20 DR
9 6@24 6@15 DR
10 6@19 DR DR
For SI: 1 inch = 25.4 mm; 1 foot = 0.3048 m; 1 psf/ft = 0.1571 kN/m2/m
1 Table values are based on reinforcing bars with a minimum yield strength of 60,000 psi (420 MPa), concrete with a minimum specified compressive strength of 2,500 psi (17.2 MPa), and vertical reinforcement being located at the centerline of the wall. See Section 3.3.
2 Vertical reinforcement with a yield strength of less than 60,000 psi (420 MPa) and/or bars of a different size than specified in the table are permitted in accordance with Section 2.5.7 and Table 2.3.
3 Deflection criterion is L/240, where L is the height of the basement wall in inches.
4 Interpolation shall not be permitted.
5 Where walls will retain 4 feet (1.2 m) or greater of unbalanced backfill, they shall be laterally supported at the top and bottom before backfilling.
6 Refer to Chapter 1 for the definition of unbalanced backfill height.
7 NR indicates no vertical wall reinforcement is required, except for 6-inch (152 mm) nominal walls formed with stay-in-place forming systems in which case vertical reinforcement shall be No. 4@48 inches (1219 mm) on center.
8 See Sections 3.2.3, 3.2.4 and 3.2.5 for minimum reinforcement required for basement walls supporting above-grade concrete walls.
9 See Table 2.1 for tolerance from nominal thickness permitted for flat walls.
10 DR means design is required in accordance with the applicable building code, or where there is no code in accordance with ACI 318.

Table 3.7. Minimum Vertical Reinforcement for 8-Inch (203 mm)
Nominal Flat Concrete Basement Walls1,2,3,4,5,6,8,9

Maximum unsupported wall height (ft) Maximum unbalanced backfill height7 (ft) Minimum vertical reinforcement – bar size No. and spacing (in.)
Maximum design lateral soil load
30 psf/ft 45 psf/ft 60 psf/ft
8 4 NR NR NR
5 NR NR NR
6 NR NR 6@37
7 NR 6@36 6@35
8 6@41 6@35 6@26
9 4 NR NR NR
5 NR NR NR
6 NR NR 6@35
7 NR 6@35 6@32
8 6@36 6@32 6@23
9 6@35 6@25 6@18
10 4 NR NR NR
5 NR NR NR
6 NR NR 6@35
7 NR 6@35 6@29
8 6@35 6@29 6@21
9 6@34 6@22 6@16
10 6@27 6@17 6@13
For SI: 1 inch = 25.4 mm; 1 foot = 0.3048 m; 1 psf/ft = 0.1571 kN/m2/m
1 Table values are based on reinforcing bars with a minimum yield strength of 60,000 psi (420 MPa), concrete with a minimum specified compressive strength of 2,500 psi (17.2 MPa), and vertical reinforcement being located at the centerline of the wall. See Section 3.3.
2 Vertical reinforcement with a yield strength of less than 60,000 psi (420 MPa) and/or bars of a different size than specified in the table are permitted in accordance with Section 2.5.7 and Table 2.3.
3 NR indicates no vertical reinforcement is required.
4 Deflection criterion is L/240, where L is the height of the basement wall in inches.
5 Interpolation shall not be permitted.
6 Where walls will retain 4 feet (1.2 m) or greater of unbalanced backfill, they shall be laterally supported at the top and bottom before backfilling.
7 Refer to Chapter 1 for the definition of unbalanced backfill height.
8 See Sections 3.2.3, 3.2.4 and 3.2.5 for minimum reinforcement required for basement walls supporting above-grade concrete walls.
9 See Table 2.1 for tolerance from nominal thickness permitted for flat walls.

~ Back to Top ~

Table 3.8. Minimum Vertical Reinforcement for 10-Inch (252 mm)
Nominal Flat Concrete Basement Walls1,2,3,4,5,6,8,9

Maximum unsupported wall height (ft) Maximum unbalanced backfill height7 (ft) Minimum vertical reinforcement – bar size No. and spacing (in.)
Maximum design lateral soil load
30 psf/ft 45 psf/ft 60 psf/ft
8 4 NR NR NR
5 NR NR NR
6 NR NR NR
7 NR NR NR
8 6@48 6@35 6@28
9 4 NR NR NR
5 NR NR NR
6 NR NR NR
7 NR NR 6@31
8 NR 6@31 6@28
9 6@37 6@28 6@24
10 4 NR NR NR
5 NR NR NR
6 NR NR NR
7 NR NR 6@28
8 NR 6@28 6@28
9 6@33 6@28 6@21
10 6@28 6@23 6@17
For SI: 1 inch = 25.4 mm; 1 foot = 0.3048 m; 1 psf/ft = 0.1571 kN/m2/m
1 Table values are based on reinforcing bars with a minimum yield strength of 60,000 psi (420 MPa), concrete with a minimum specified compressive strength of 2,500 psi (17.2 MPa), and vertical reinforcement being located at the centerline of the wall. See Section 3.3.
2 Vertical reinforcement with a yield strength of less than 60,000 psi (420 MPa) and/or bars of a different size than specified in the table are permitted in accordance with Section 2.5.7 and Table 2.3.
3 NR indicates no vertical reinforcement is required.
4 Deflection criterion is L/240, where L is the height of the basement wall in inches.
5 Interpolation shall not be permitted.
6 Where walls will retain 4 feet (1.2 m) or greater of unbalanced backfill, they shall be laterally supported at the top and bottom before backfilling.
7 Refer to Chapter 1 for the definition of unbalanced backfill height.
8 See Sections 3.2.3, 3.2.4 and 3.2.5 for minimum reinforcement required for basement walls supporting above-grade concrete walls.
9 See Table 2.1 for tolerance from nominal thickness permitted for flat walls.

Table 4.1. Minimum Vertical Reinforcement for Flat Above-Grade Walls1,2,3,4,5,11

Basic wind speed (mph) Maximum unsupported wall height per story (ft) Minimum vertical reinforcement – bar size No. and spacing (in.)6,7,8
Nominal9 wall thickness (in.)
Exposure category 4 6 8 10
B C D Top10 Top10 Top10 Top10 Top10 Top10 Top10 Top10
85 - - 8 4@48 4@48 4@48 4@48 4@48 4@48 4@48 4@48
9 4@48 4@43 4@48 4@48 4@48 4@48 4@48 4@48
10 4@47 4@36 4@48 4@48 4@48 4@48 4@48 4@48
90 - - 8 4@48 4@47 4@48 4@48 4@48 4@48 4@48 4@48
9 4@48 4@39 4@48 4@48 4@48 4@48 4@48 4@48
10 4@42 4@34 4@48 4@48 4@48 4@48 4@48 4@48
100 85 - 8 4@48 4@40 4@48 4@48 4@48 4@48 4@48 4@48
9 4@42 4@34 4@48 4@48 4@48 4@48 4@48 4@48
10 4@34 4@34 4@48 4@48 4@48 4@48 4@48 4@48
110 90 85 8 4@44 4@34 4@48 4@48 4@48 4@48 4@48 4@48
9 4@34 4@34 4@48 4@48 4@48 4@48 4@48 4@48
10 4@34 4@31 4@48 4@37 4@48 4@48 4@48 4@48
120 100 90 8 4@36 4@34 4@48 4@48 4@48 4@48 4@48 4@48
9 4@34 4@32 4@48 4@38 4@48 4@48 4@48 4@48
10 4@30 4@27 4@48 5@48 4@48 4@48 4@48 4@48
130 110 100 8 4@34 4@34 4@48 4@48 4@48 4@48 4@48 4@48
9 4@32 4@28 4@33 4@48 4@48 4@48 4@48 4@48
10 4@26 4@23 4@48 5@43 4@48 4@48 4@48 4@48
140 120 110 8 4@34 4@30 4@48 4@35 4@48 4@48 4@48 4@48
9 4@27 4@24 4@48 5@44 4@48 4@48 4@48 4@48
10 4@21 4@19 5@41 5@37 4@48 4@48 4@48 4@48
150 130 120 8 4@29 4@26 4@48 5@47 4@48 4@48 4@48 4@48
9 4@23 4@20 5@43 5@38 4@48 4@48 4@48 4@48
10 4@18 4@16 5@35 5@34 4@48 4@48 4@48 4@48
166 140 130 8 4@25 4@22 5@47 5@41 4@48 4@48 4@48 4@48
9 4@19 4@17 5@37 5@34 4@48 4@48 4@48 4@48
10 4@15 4@14 5@34 5@34 4@48 5@37 4@48 4@48
179 150 140 8 4@21 4@19 5@40 5@36 4@48 4@48 4@48 4@48
9 4@16 4@15 5@34 5@34 5@35 5@39 4@48 4@48
10 DR DR 5@34 5@31 4@48 6@46 4@48 4@48
192 163 150 8 4@18 4@16 5@35 5@34 4@48 5@43 4@48 4@48
9 4@14 4@13 5@34 5@34 4@48 6@48 4@48 4@48
10 DR DR 5@29 5@27 6@43 6@40 4@48 4@48
For SI: 1 inch = 25.4 mm; 1 foot = 0.3048 m; 1 mph = 0.4470 m/s

Table 4.4. Minimum Vertical Reinforcement for Flat, Waffle- and Screen-Grid Stem Walls Designed Continuous With Above-Grade Walls1,2,3,4,5,19,20

Basic wind speed (mph) Height of stem wall,9,10 (ft) Max. design lateral soil load (psf/ft) Max. unsupported height of above-grade wall (ft) Min. vertical reinforcement – bar size No. and spacing (in.)6,7,8
Wall type and nominal thickness, (in.)18
Exposure category Flat Waffle Screen
B C D 4 6 8 10 6 8 6
90 - - 3 30 8 4@30 4@36 4@48 4@48 4@22 4@26 4@21
10 4@24 5@44 4@38 4@48 4@1715 4@21 4@1715
60 10 4@20 5@37 5@48 4@41 4@1516 4@18 4@1416
6 30 10 DR 5@2111 6@3512 6@41 DR 4@1017 DR
60 10 DR DR 6@2613 6@2814 DR DR DR
110 90 85 3 30 8 4@22 5@42 4@37 4@46 4@16 4@20 4@16
10 4@17 5@34 5@44 4@35 4@1215 4@17 4@1215
60 10 4@15 5@34 5@39 5@48 4@1116 4@17 4@1116
6 30 10 DR 5@1811 6@3512 6@35 DR 4@917 DR
60 10 DR DR 6@2313 6@2814 DR DR DR
120 100 90 3 30 8 4@19 5@37 5@48 4@40 4@14 4@17 4@14
10 4@14 5@34 5@38 5@48 4@1115 4@17 4@1015
60 10 4@13 5@33 6@48 5@43 4@1016 4@16 4@916
6 30 10 DR 5@1611 6@3312 6@32 DR 4@817 DR
60 10 DR DR 6@2213 6@2814 DR DR DR
140 120 110 3 30 8 4@14 5@34 5@38 5@48 4@11 4@17 4@10
10 DR 5@28 6@41 5@36 DR 4@13 DR
60 10 DR 5@29 6@43 5@38 DR 4@12 DR
6 30 10 DR 5@13 6@2712 6@28 DR DR DR
60 10 DR DR 6@1913 6@2514 DR DR DR
166 140 130 3 30 8 DR 5@28 6@41 5@37 DR 4@13 DR
10 DR 5@20 6@35 6@39 DR 4@10 DR
60 10 DR 5@19 6@35 6@37 DR 4@9 DR
6 30 10 DR DR 6@21 6@28 DR DR DR
60 10 DR DR 6@16 6@2114 DR DR DR
179 150 140 3 30 8 DR 5@24 6@36 6@46 DR 4@12 DR
10 DR 5@18 6@35 6@34 DR 4@8 DR
60 10 DR 5@17 6@34 6@32 DR 4@8 DR
6 30 10 DR DR 6@19 6@25 DR DR DR
60 10 DR DR 6@15 6@20 DR DR DR
192 163 150 3 30 8 DR 5@21 6@35 6@41 DR 4@10 DR
10 DR 5@15 6@31 6@30 DR 4@7 DR
60 10 DR 5@15 6@30 6@29 DR DR DR
6 30 10 DR DR 6@17 6@22 DR DR DR
60 10 DR DR 6@14 6@18 DR DR DR
For SI: 1 inch = 25.4 mm; 1 foot = 0.3048 m; 1 mph = 0.4470 m/s; 1 psf/ft = 0.1571 kN/m2/m

Table 7.3. Maximum Allowable Clear Spans for 4-inch Nominal Thick Flat Lintels in Load-Bearing Walls1,2,3,4,5,6,13 Roof Clear Span 40 feet and Floor Clear Span 32 feet

Lintel Depth7, D(in.) Number of bars and bar size in top and bottom of lintel Steel yield strength8, fy(psi) Loading condition determined from Table 7.2
1 2 3 4 5
Maximum ground snow load (psf)
30 70 30 70 30 70 30 70
Maximum clear span of lintel (ftinches)
8 Span without stirrups9,10 2-Mar 4-Mar 4-Feb 6-Feb 2-Feb 1-Feb Feb-00 Feb-00 Feb-00
1 – #4 40,000 2-May 5-May 1-Apr 3-Apr 10-Mar 7-Mar 4-Mar 9-Feb 9-Feb
60,000 2-Jun 5-Jun 11-Apr 1-May 6-Apr 2-Apr 8-Mar 11-Feb 10-Feb
1 – #5 40,000 3-Jun 7-Jun May-00 2-May 6-Apr 2-Apr 8-Mar 11-Feb 10-Feb
60,000 DR DR DR DR DR DR DR DR DR
Center distance A11,12 1-Jan 2-Jan 0-8 0-9 0-7 0-6 0-5 0-4 0-4
12 Span without stirrups9,10 4-Mar 7-Mar 9-Feb 11-Feb 8-Feb 6-Feb 5-Feb 2-Feb 2-Feb
1 – #4 40,000 7-Jun Jul-00 4-May 7-May May-00 9-Apr 44 8-Mar 7-Mar
60,000 11-Jul 6-Aug 6-Jun 9-Jun Jun-00 9-May 3-May 5-Apr 4-Apr
1 – #5 40,000 1-Aug 8-Aug 7-Jun 10-Jun 2-Jun 10-May 4-May 6-Apr 5-Apr
60,000 8-Sep 4-Oct 11-Jul 2-Aug 4-Jul 11-Jun 2-Jun 10-Apr 8-Apr
2 – #4
1 – #6
40,000 1-Sep 8-Sep 4-Jul 8-Jul 10-Jun 6-Jun Jun-00 10-Apr 8-Apr
60,000 DR DR DR DR DR DR DR DR DR
Center distance A11,12 8-Jan 11-Jan 1-Jan 3-Jan Jan-00 0-11 0-9 0-6 0-6
16 Span without stirrups9,10 7-Apr May-00 11-Mar Apr-00 8-Mar 7-Mar 4-Mar 1-Mar Mar-00
1 – #4 40,000 8-Jun 3-Jul 6-May 9-May 2-May 11-Apr 6-Apr 10-Mar 8-Mar
60,000 3-Sep 1-Oct 9-Jul Aug-00 2-Jul 10-Jun 3-Jun 4-May 2-May
1 – #5 40,000 6-Sep 4-Oct 10-Jul 2-Aug 4-Jul 11-Jun 5-Jun 5-May 3-May
60,000 5-Nov 5-Dec 6-Sep 10-Sep 10-Aug 4-Aug 9-Jul 6-Jun 4-Jun
2 – #4
1 – #6
40,000 7-Oct 7-Nov 10-Aug 2-Sep 3-Aug 9-Jul 2-Jul 1-Jun 11-May
60,000 9-Dec 13-10 7-Oct Nov-00 10-Sep 4-Sep 7-Aug 9-Jun 6-Jun
2 – #5 40,000 13-0 14-1 9-Oct 2-Nov 11-Sep 2-Sep 2-Aug 6-Jun 3-Jun
60,000 DR DR DR DR DR 0-6 DR DR DR
Center distance A11,12 3-Feb 8-Feb 7-Jan 8-Jan 4-Jan 3-Jan Jan-00 0-9 0-8
20 Span without stirrups9,10 9-May 5-Jun May-00 2-May 9-Apr 7-Apr 4-Apr 11-Mar 11-Mar
1 – #4 40,000 5-Jul 2-Aug 3-Jun 6-Jun 10-May 7-May 1-May 4-Apr 2-Apr
60,000 Sep-00 Oct-00 8-Jul 11-Jul 1-Jul 9-Jun 3-Jun 3-May 1-May
1 – #5 40,000 2-Sep 2-Oct 9-Jul 1-Aug 3-Jul 11-Jun 4-Jun 4-May 2-May
60,000 9-Dec 14-2 10-Oct 3-Nov 1-Oct 7-Sep 10-Aug 5-Jul 3-Jul
2 – #4
1 – #6
40,000 10-Nov 13-2 1-Oct 5-Oct 4-Sep 11-Aug 2-Aug 11-Jun 9-Jun
60,000 14-4 15-10 1-Dec 7-Dec 3-Nov 9-Oct 11-Sep 4-Aug 1-Aug
2 – #5 40,000 14-7 16-2 4-Dec 9-Dec 4-Nov 6-Oct 5-Sep 7-Jul 3-Jul
60,000 17-5 19-3 14-9 15-3 13-5 4-Dec Nov-00 8-Aug 4-Aug
2 – #6 40,000 16-4 18-11 7-Dec 13-3 4-Nov 6-Oct 5-Sep 7-Jul 3-Jul
60,000 DR DR DR DR DR DR DR DR DR
Center distance A11,12 9-Feb 5-Mar Feb-00 2-Feb 9-Jan 7-Jan 4-Jan 0-11 0-11
24 Span without stirrups9,10 11-Jun 9-Jul 1-Jun 3-Jun 9-May 7-May 3-May 9-Apr 8-Apr
1 – #4 40,000 Aug-00 Sep-00 11-Jun 2-Jul 5-Jun 2-Jun 8-May 9-Apr 8-Apr
60,000 9-Sep Nov-00 5-Aug 9-Aug 10-Jul 6-Jul 11-Jun 10-May 8-May
1 – #5 40,000 Oct-00 3-Nov 7-Aug 11-Aug Aug-00 7-Jul Jul-00 11-May 9-May
60,000 13-11 15-8 Dec-00 5-Dec 2-Nov 7-Oct 10-Sep 3-Aug Aug-00
2 – #4
1 – #6
40,000 11-Dec 14-6 2-Nov 6-Nov 5-Oct 10-Sep 1-Sep 8-Jul 5-Jul
60,000 15-7 17-7 13-6 13-11 7-Dec 11-Nov Nov-00 3-Sep Sep-00
2 – #5 40,000 15-11 17-11 13-9 14-3 8-Dec 9-Nov 8-Oct 7-Aug 4-Aug
60,000 19-1 21-6 16-5 17-1 15-1 14-0 6-Dec 11-Sep 7-Sep
2 – #6 40,000 17-7 21-1 14-1 14-10 8-Dec 9-Nov 8-Oct 7-Aug 4-Aug
60,000 DR DR DR DR DR DR DR DR DR
Center distance A11,12 3-Mar 1-Apr 5-Feb 7-Feb 1-Feb 11-Jan 7-Jan 2-Jan 1-Jan
For SI: 1 inch = 25.4 mm; 1 psf = 0.0479 kN/m2; 1 ft = 0.3048 m; Grade 40 = 280 MPa; Grade 60 = 420 MPa
See page 7-7 for notes.

Table 7.4. Maximum Allowable Clear Spans for 4-inch Nominal Thick Flat Lintels in Load-Bearing Walls1,2,3,4,5,6,13 Roof Clear Span 32 feet and Floor Clear Span 24 feet

Lintel Depth7, D(in.) Number of bars and bar size in top and bottom of lintel Steel yield strength8, fy(psi) Loading condition determined from Table 7.2
1 2 3 4 5
Maximum ground snow load (psf)
30 70 30 70 30 70 30 70
Maximum clear span of lintel (ft–inches)
8 Span without stirrups9,10 3-9 3-11 2-8 2-10 2-6 2-3 2-1 2-0 2-0
1 – #4 40,000 5-10 6-0 4-7 4-9 4-3 4-0 3-8 3-1 3-0
60,000 7-0 7-2 5-5 5-8 5-1 4-9 4-3 3-4 3-2
1 – #5 40,000 7-1 7-3 5-6 5-9 5-2 4-10 4-3 3-4 3-2
60,000 DR DR DR DR DR DR DR DR DR
Center distance A11,12 1-5 1-6 0-10 0-11 0-9 0-8 0-6 0-5 0-4
12 Span without stirrups9,10 3-10 4-1 3-1 3-2 2-10 2-9 2-7 2-4 2-3
1 – #4 40,000 7-5 7-10 6-0 6-3 5-6 5-2 4-9 4-0 3-11
60,000 9-0 9-6 7-3 7-6 6-8 6-3 5-9 4-10 4-9
1 – #5 40,000 9-2 9-8 7-4 7-8 6-10 6-5 5-10 4-11 4-10
60,000 10-11 11-6 8-9 9-2 8-2 7-8 7-0 5-6 5-3
2 – #4
1 – #6
40,000 10-2 10-9 8-2 8-6 7-7 7-2 6-7 5-6 5-3
60,000 12-1 12-9 9-9 10-2 8-11 8-0 7-1 5-6 5-3
Center distance A11,12 2-2 2-5 1-5 1-6 1-2 1-1 0-11 0-8 0-7
16 Span without stirrups9,10 5-2 5-8 4-3 4-5 4-0 3-10 3-7 3-3 3-2
1 – #4 40,000 7-6 8-1 6-2 6-5 5-9 5-4 4-11 4-2 4-1
60,000 10-5 11-3 8-7 8-11 8-0 7-6 6-11 5-10 5-8
1 – #5 40,000 10-7 11-5 8-9 9-1 8-2 7-7 7-0 5-11 5-9
60,000 12-9 13-10 10-7 11-0 9-10 9-2 8-6 7-2 6-11
2 – #4
1 – #6
40,000 11-11 12-10 9-10 10-3 9-1 8-6 7-10 6-8 6-5
60,000 14-3 15-5 11-9 12-3 10-11 10-3 9-5 7-8 7-4
2 – #5 40,000 14-6 15-8 12-0 12-6 11-2 10-5 9-4 7-4 7-0
60,000 DR DR DR DR DR DR DR DR DR
Center distance A11,12 2-10 3-4 1-11 2-1 1-8 1-6 1-3 0-11 0-10
20 Span without stirrups9,10 6-5 7-2 5-6 5-8 5-2 4-10 4-7 4-2 4-1
1 – #4 40,000 8-3 9-1 7-0 7-3 6-6 6-1 5-7 4-9 4-7
60,000 10-1 11-1 8-6 8-10 7-11 7-5 6-10 5-9 5-7
1 – #5 40,000 10-3 11-4 8-8 9-0 8-1 7-7 7-0 5-11 5-9
60,000 14-3 15-8 12-0 12-6 11-2 10-6 9-8 8-2 7-11
2 – #4
1 – #6
40,000 13-3 14-7 11-2 11-8 10-5 9-9 9-0 7-7 7-4
60,000 15-11 17-7 13-6 14-0 12-6 11-9 10-10 9-2 8-11
2 – #5 40,000 16-3 17-11 13-9 14-3 12-9 11-12 10-8 8-6 8-2
60,000 19-4 21-4 16-5 17-1 15-3 14-3 12-7 9-10 9-5
2 – #6 40,000 19-0 21-0 14-10 15-10 13-3 12-0 10-8 8-6 8-2
60,000 DR DR DR DR DR DR DR DR DR
Center distance A11,12 3-5 4-2 2-6 2-8 2-2 1-10 1-7 1-2 1-1
24 Span without stirrups9,10 7-8 8-9 6-8 6-11 6-3 5-11 5-7 5-1 5-0
1 – #4 40,000 8-11 10-0 7-8 8-0 7-2 6-9 6-2 5-3 5-1
60,000 10-10 12-2 9-5 9-9 8-9 8-2 7-7 6-5 6-2
1 – #5 40,000 11-1 12-5 9-7 10-0 8-11 8-4 7-8 6-6 6-4
60,000 15-5 17-4 13-4 13-11 12-5 11-8 10-9 9-1 8-10
2 – #4
1 – #6
40,000 14-3 16-1 12-5 12-11 11-6 10-9 9-11 8-5 8-2
60,000 17-3 19-5 15-0 15-7 13-11 13-1 12-0 10-2 9-11
2 – #5 40,000 17-7 19-10 15-3 15-10 14-2 13-4 12-0 9-7 9-3
60,000 21-2 23-9 18-4 19-0 17-0 15-11 14-3 11-3 10-9
2 – #6 40,000 20-9 23-4 16-6 17-7 14-9 13-5 12-0 9-7 9-3
60,000 DR DR DR DR DR DR DR DR DR
Center distance A11,12 4-0 5-1 3-0 3-3 2-7 2-3 1-11 1-5 1-4
For SI: 1 inch = 25.4 mm; 1 psf = 0.0479 kN/m2; 1 ft = 0.3048 m; Grade 40 = 280 MPa; Grade 60 = 420 MPa
See page 7-7 for notes.

~ Back to Top ~

Table 7.5. Maximum Allowable Clear Spans for 6-inch Nominal Thick Flat Lintels in Load-Bearing Walls1,2,3,4,5,6,13 Roof Clear Span 40 feet and Floor Clear Span 32 feet

Lintel Depth7, D (in.) Number of barsand bar size in top and bottom of lintel Steel yield strength8, fy(psi) Loading condition determined from Table 7.2
1 2 3 4 5
Maximum ground snow load (psf)
30 70 30 70 30 70 30 70
Maximum clear span of lintel (ft–inches)
8 Span without stirrups9,10 4-2 4-8 3-1 3-3 2-10 2-6 2-3 2-0 2-0
1 – #4 40,000 5-1 5-5 4-2 4-3 3-10 3-6 3-3 2-8 2-7
60,000 6-2 6-7 5-0 5-2 4-8 4-2 3-11 3-3 3-2
1 – #5 40,000 6-3 6-8 5-1 5-3 4-9 4-3 4-0 3-3 3-2
60,000 7-6 8-0 6-1 6-4 5-8 5-1 4-9 3-8 3-6
2 – #4
1 – #6
40,000 7-0 7-6 5-8 5-11 5-3 4-9 4-5 3-8 3-6
60,000 DR DR DR DR DR DR DR DR DR
Center distance A11,12 1-7 1-10 1-1 1-2 0-11 0-9 0-8 0-5 0-5
12 Span without stirrups9,10 4-2 4-8 3-5 3-6 3-2 2-11 2-9 2-5 2-4
1 – #4 40,000 5-7 6-1 4-8 4-10 4-4 3-11 3-8 3-0 2-11
60,000 7-9 8-6 6-6 6-9 6-1 5-6 5-1 4-3 4-1
1 – #5 40,000 7-11 8-8 6-8 6-11 6-2 5-7 5-2 4-4 4-2
60,000 9-7 10-6 8-0 8-4 7-6 6-9 6-3 5-2 5-1
2 – #4
1 – #6
40,000 8-11 9-9 7-6 7-9 6-11 6-3 5-10 4-10 4-8
60,000 10-8 11-9 8-12 9-4 8-4 7-6 7-0 5-10 5-8
2 – #5 40,000 10-11 12-0 9-2 9-6 8-6 7-8 7-2 5-6 5-3
60,000 12-11 14-3 10-10 11-3 10-1 9-0 8-1 6-1 5-10
2 – #6 40,000 12-9 14-0 10-8 11-1 9-7 8-1 7-3 5-6 5-3
60,000 DR DR DR DR DR DR DR DR DR
Center distance A11,12 2-6 3-0 1-9 1-10 1-6 1-3 1-1 0-9 0-8
16 Span without stirrups9,10 5-7 6-5 4-9 4-11 4-5 4-0 3-10 3-4 3-4
1 – #4 40,000 6-5 7-2 5-6 5-9 5-2 4-8 4-4 3-7 3-6
60,000 7-10 8-9 6-9 7-0 6-3 5-8 5-3 4-4 4-3
1 – #5 40,000 7-11 8-11 6-10 7-1 6-5 5-9 5-4 4-5 4-4
60,000 11-1 12-6 9-7 9-11 8-11 8-0 7-6 6-2 6-0
2 – #4
1 – #6
40,000 10-3 11-7 8-10 9-2 8-3 7-6 6-11 5-9 5-7
60,000 12-5 14-0 10-9 11-1 10-0 9-0 8-5 7-0 6-9
2 – #5 40,000 12-8 14-3 10-11 11-4 10-2 9-2 8-7 6-9 6-6
60,000 15-2 17-1 13-1 13-7 12-3 11-0 10-3 7-11 7-7
2 – #6 40,000 14-11 16-9 12-8 13-4 11-4 9-8 8-8 6-9 6-6
60.000 DR DR DR DR DR DR DR DR DR
Center distance A11,12 3-3 4-1 2-5 2-7 2-1 1-9 1-6 1-0 1-0
20 Span without stirrups9,10 6-11 8-2 6-1 6-3 5-8 5-2 4-11 4-4 4-3
1 – #5 40,000 8-9 10-1 7-9 8-0 7-3 6-6 6-1 5-1 4-11
60,000 10-8 12-3 9-5 9-9 8-10 8-0 7-5 6-2 6-0
2 – #4
1 – #6
40,000 9-11 11-4 8-9 9-1 8-2 7-4 6-10 5-8 5-7
60,000 13-9 15-10 12-2 12-8 11-5 10-3 9-7 7-11 7-9
2 – #5 40,000 14-0 16-2 12-5 12-11 11-7 10-6 9-9 7-11 7-8
60,000 16-11 19-6 15-0 15-6 14-0 12-7 11-9 9-1 8-9
2 – #6 40,000 16-7 19-1 14-7 15-3 13-1 11-3 10-2 7-11 7-8
60,000 19-11 22-10 17-4 18-3 15-6 13-2 11-10 9-1 8-9
Center distance A11,12 3-11 5-2 3-1 3-3 2-8 2-2 1-11 1-4 1-3
24 Span without stirrups9,10 8-2 9-10 7-4 7-8 6-11 6-4 5-11 5-3 5-2
1 – #5 40,000 9-5 11-1 8-7 8-10 8-0 7-3 6-9 5-7 5-5
60,000 11-6 13-6 10-5 10-9 9-9 8-9 8-2 6-10 6-8
2 – #4
1 – #6
40,000 10-8 12-6 9-8 10-0 9-0 8-2 7-7 6-4 6-2
60,000 12-11 15-2 11-9 12-2 11-0 9-11 9-3 7-8 7-6
2 – #5 40,000 15-2 17-9 13-9 14-3 12-10 11-7 10-10 9-0 8-9
60,000 18-4 21-6 16-7 17-3 15-6 14-0 13-1 10-4 10-0
2 – #6 40,000 18-0 21-1 16-4 16-11 14-10 12-9 11-8 9-2 8-11
60,000 21-7 25-4 19-2 20-4 17-2 14-9 13-4 10-4 10-0
Center distance A11,12 4-6 6-2 3-8 4-0 3-3 2-8 2-3 1-7 1-6

Table 7.6. Maximum Allowable Clear Spans for 6-inch Nominal Thick Flat Lintels in Load-Bearing Walls1,2,3,4,5,6,13 Roof Clear Span 32 feet and Floor Clear Span 24 feet

Lintel Depth7, D (in.) Number of bars and bar size in top and bottom of lintel Steel yield strength8, fy(psi) Loading condition determined from Table 7.2
1 2 3 4 5
Maximum ground snow load (psf)
30 70 30 70 30 70 30 70
Maximum clear span of lintel (ft–inches)
8 Span without stirrups9,10 5-1 5-6 3-8 3-10 3-3 2-9 2-6 2-0 2-0
1 – #4 40,000 5-9 6-1 4-7 4-10 4-3 3-9 3-6 2-11 2-10
60,000 6-11 7-4 5-7 5-9 5-2 4-6 4-3 3-6 3-5
1 – #5 40,000 7-0 7-5 5-8 5-11 5-3 4-8 4-4 3-7 3-6
60,000 8-5 8-11 6-9 7-1 6-3 5-6 5-2 4-1 3-11
2 – #4
1 – #6
40,000 7-10 8-4 6-4 6-7 5-10 5-2 4-10 4-0 3-10
60,000 DR DR DR DR DR DR DR DR DR
Center distance A11,12 2-0 2-3 1-4 1-5 1-2 0-11 0-9 0-6 0-6
12 Span without stirrups9,10 4-9 5-4 3-10 4-0 3-6 3-1 2-11 2-6 2-6
1 – #4 40,000 6-3 6-9 5-2 5-5 4-10 4-3 4-0 3-3 3-2
60,000 8-8 9-6 7-3 7-7 6-9 5-11 5-6 4-7 4-6
1 – #5 40,000 8-10 9-8 7-5 7-8 6-11 6-1 5-8 4-8 4-6
60,000 10-8 11-8 8-11 9-4 8-4 7-4 6-10 5-8 5-6
2 – #4
1 – #6
40,000 9-11 10-10 8-4 8-8 7-9 6-10 6-4 5-3 5-1
60,000 11-11 13-0 10-0 10-5 9-3 8-2 7-7 6-3 6-2
2 – #5 40,000 12-2 13-3 10-2 10-7 9-6 8-4 7-9 6-2 5-11
60,000 14-5 15-9 12-1 12-7 11-3 9-11 9-2 6-10 6-7
2 – #6 40,000 14-3 15-6 11-11 12-4 11-1 9-3 8-3 6-2 5-11
60,000 DR DR DR DR DR DR DR DR DR
Center distance A11,12 3-1 3-8 2-2 2-4 1-10 1-5 1-3 0-10 0-10
16 Span without stirrups9,10 6-4 7-4 5-4 5-7 4-11 4-4 4-1 3-6 3-6
1 – #4 40,000 7-1 8-0 6-2 6-5 5-9 5-0 4-8 3-11 3-9
60,000 8-8 9-9 7-6 7-9 7-0 6-2 5-9 4-9 4-7
1 – #5 40,000 8-10 9-11 7-8 7-11 7-1 6-3 5-10 4-10 4-8
60,000 12-3 13-10 10-8 11-1 9-11 8-9 8-1 6-9 6-7
2 – #4
1 – #6
40,000 11-5 12-10 9-10 10-3 9-2 8-1 7-6 6-3 6-1
60,000 13-9 15-6 11-11 12-5 11-1 9-9 9-1 7-6 7-4
2 – #5 40,000 14-0 15-9 12-2 12-8 11-4 10-0 9-3 7-6 7-3
60,000 16-10 18-11 14-7 15-2 13-7 12-0 11-2 8-10 8-6
2 – #6 40,000 16-6 18-7 14-4 14-11 13-4 11-0 9-10 7-6 7-3
60.000 DR DR DR DR DR DR DR DR DR
Center distance A11,12 4-0 5-0 3-0 3-3 2-7 2-0 1-9 1-2 1-2
20 Span without stirrups9,10 7-9 9-4 6-9 7-1 6-3 5-7 5-3 4-6 4-5
1 – #5 40,000 9-8 11-2 8-7 9-0 8-0 7-1 6-7 5-6 5-4
60,000 11-9 13-7 10-6 10-11 9-9 8-8 8-0 6-8 6-6
2 – #4
1 – #6
40,000 10-10 12-7 9-9 10-1 9-1 8-0 7-5 6-2 6-0
60,000 15-2 17-6 13-6 14-1 12-7 11-2 10-4 8-7 8-5
2 – #5 40,000 15-5 17-10 13-10 14-4 12-10 11-4 10-7 8-9 8-6
60,000 18-7 21-6 16-8 17-4 15-6 13-8 12-9 10-2 9-10
2 – #6 40,000 18-3 21-1 16-4 17-0 15-3 12-8 11-5 8-9 8-6
60,000 21-10 24-10 19-6 20-4 18-2 15-0 13-5 10-2 9-10
Center distance A11,12 4-9 6-4 3-9 4-1 3-3 2-7 2-3 1-6 1-5
24 Span without stirrups9,10 9-0 11-2 8-3 8-7 7-7 6-9 6-4 5-6 5-5
1 – #5 40,000 10-3 12-2 9-6 9-10 8-10 7-10 7-3 6-0 5-11
60,000 12-7 14-10 11-7 12-0 10-9 9-6 8-10 7-4 7-2
2 – #4
1 – #6
40,000 11-7 13-9 10-8 11-1 10-0 8-10 8-3 6-10 6-8
60,000 14-2 16-9 13-0 13-6 12-2 10-9 10-0 8-4 8-1
2 – #5 40,000 16-7 19-7 15-3 15-10 14-3 12-7 11-8 9-9 9-6
60,000 20-0 23-8 18-5 19-2 17-2 15-2 14-2 11-6 11-1
2 – #6 40,000 19-8 23-3 18-1 18-9 16-10 14-5 13-0 10-1 9-9
60,000 23-7 22-10 21-9 22-7 20-3 16-8 15-0 11-6 11-1
Center distance A11,12 5-4 7-6 4-7 4-11 4-0 3-1 2-8 1-10 1-9
For SI: 1 inch = 25.4 mm; 1 psf = 0.0479 kN/m2; 1 ft = 0.3048 m; Grade 40 = 280 MPa; Grade 60 = 420 MPa
See Page 7-7 for notes.

Table 7.7. Maximum Allowable Clear Spans for 8-inch Nominal Thick Flat Lintels in Load-Bearing Walls1,2,3,4,5,6,13 Roof Clear Span 40 feet and Floor Clear Span 32 feet

Lintel Depth7, D(in.) Number of bars and bar size in top and bottom of lintel Steel yield strength8, fy(psi) Loading condition determined from Table 7.2
1 2 3 4 5
Maximum ground snow load (psf)
30 70 30 70 30 70 30 70
Maximum clear span of lintel (ft–inches)
8 8 Span without stirrups9,10 4-4 4-9 3-7 3-9 3-4 2-10 2-7 2-1 2-0
1 – #4 40,000 4-4 4-9 3-7 3-9 3-4 2-11 2-9 2-3 2-2
60,000 6-1 6-7 5-0 5-3 4-8 4-0 3-9 3-1 3-0
1 – #5 40,000 6-2 6-9 5-2 5-4 4-9 4-1 3-10 3-2 3-1
60,000 7-5 8-1 6-2 6-5 5-9 4-11 4-7 3-9 3-8
2 – #4
1 – #6
40,000 6-11 7-6 5-9 6-0 5-4 4-7 4-4 3-6 3-5
60,000 8-3 9-0 6-11 7-2 6-5 5-6 5-2 4-2 4-1
2 – #5 40,000 8-5 9-2 7-0 7-3 6-6 5-7 5-3 4-2 4-0
60,000 DR DR DR DR DR DR DR DR DR
Center distance A11,12 2-1 2-6 1-5 1-6 1-3 0-11 0-10 0-6 0-6
12 12 Span without stirrups9,10 4-10 5-8 4-0 4-2 3-9 3-2 3-0 2-7 2-6
1 – #4 40,000 5-5 6-1 4-8 4-10 4-4 3-9 3-6 2-10 2-10
60,000 6-7 7-5 5-8 5-11 5-4 4-7 4-3 3-6 3-5
1 – #5 40,000 6-9 7-7 5-9 6-0 5-5 4-8 4-4 3-7 3-6
60,000 9-4 10-6 8-1 8-4 7-6 6-6 6-1 5-0 4-10
2 – #4
1 – #6
40,000 8-8 9-9 7-6 7-9 7-0 6-0 5-8 4-7 4-6
60,000 10-6 11-9 9-1 9-5 8-5 7-3 6-10 5-7 5-5
2 – #5 40,000 10-8 12-0 9-3 9-7 8-7 7-5 6-11 5-6 5-4
60,000 12-10 14-5 11-1 11-6 10-4 8-11 8-4 6-7 6-4
2 – #6 40,000 12-7 14-2 10-10 11-3 10-2 8-3 7-6 5-6 5-4
60,000 DR DR DR DR DR DR DR DR DR
Center distance A11,12 3-2 4-0 2-4 2-6 2-0 1-6 1-4 0-11 0-10
16 Span without stirrups9,10 6-5 7-9 5-7 5-10 5-2 4-5 4-2 3-7 3-6
1 – #4 40,000 6-2 7-1 5-6 5-8 5-1 4-5 4-2 3-5 3-4
60,000 7-6 8-8 6-8 6-11 6-3 5-5 5-1 4-2 4-0
1 – #5 40,000 7-8 8-10 6-10 7-1 6-4 5-6 5-2 4-3 4-1
60,000 9-4 10-9 8-4 8-7 7-9 6-8 6-3 5-2 5-0
2 – #4
1 – #6
40,000 8-8 10-0 7-8 8-0 7-2 6-2 5-10 4-9 4-8
60,000 12-0 13-11 10-9 11-2 10-0 8-8 8-1 6-8 6-6
2 – #5 40,000 12-3 14-2 11-0 11-4 10-3 8-10 8-3 6-9 6-7
60,000 14-10 17-2 13-3 13-8 12-4 10-8 10-0 7-11 7-8
2 – #6 40,000 14-6 16-10 13-0 13-5 12-1 10-1 9-2 6-11 6-8
60.000 17-5 20-2 15-7 16-1 14-6 11-10 10-8 7-11 7-8
Center distance A11,12 4-1 5-5 3-3 3-6 2-10 2-1 1-10 1-3 1-2
20 Span without stirrups9,10 7-10 9-10 7-1 7-5 6-7 5-8 5-4 4-7 4-6
1 – #5 40,000 8-4 9-11 7-8 8-0 7-2 6-3 5-10 4-9 4-8
60,000 10-2 12-1 9-5 9-9 8-9 7-7 7-1 5-10 5-8
2 – #4
1 – #6
40,000 9-5 11-3 8-8 9-0 8-1 7-0 6-7 5-5 5-3
60,000 11-6 13-8 10-7 11-0 9-11 8-7 8-0 6-7 6-5
2 – #5 40,000 11-9 13-11 10-10 11-2 10-1 8-9 8-2 6-8 6-7
60,000 16-4 19-5 15-0 15-7 14-0 12-2 11-4 9-3 9-0
2 – #6 40,000 16-0 19-0 14-9 15-3 13-9 11-10 10-10 8-3 8-0
60,000 19-3 22-11 17-9 18-5 16-7 13-7 12-4 9-3 9-0
Center distance A11,12 4-10 6-10 4-1 4-5 3-7 2-8 2-4 1-7 1-6
24 Span without stirrups9,10 9-2 11-9 8-7 8-11 8-0 6-11 6-6 5-7 5-6
1 – #5 40,000 8-11 10-10 8-6 8-9 7-11 6-10 6-5 5-3 5-2
60,000 10-11 13-3 10-4 10-8 9-8 8-4 7-10 6-5 6-3
2 – #4
1 – #6
40,000 10-1 12-3 9-7 9-11 8-11 7-9 7-3 6-0 5-10
60,000 12-3 15-0 11-8 12-1 10-11 9-5 8-10 7-3 7-1
2 – #5 40,000 12-6 15-3 11-11 12-4 11-1 9-7 9-0 7-5 7-3
60,000 17-6 21-3 16-7 17-2 15-6 13-5 12-7 10-4 10-1
2 – #6 40,000 17-2 20-11 16-3 16-10 15-3 13-2 12-4 9-7 9-4
60,000 20-9 25-3 19-8 20-4 18-5 15-4 14-0 10-7 10-3
Center distance A11,12 5-6 8-1 4-11 5-3 4-4 3-3 2-10 1-11 1-10
For SI: 1 inch = 25.4 mm; 1 psf = 0.0479 kN/m2; 1 ft = 0.3048 m; Grade 40 = 280 MPa; Grade 60 = 420 MPa
Top and bottom reinforcement for lintels without stirrups shown in shaded cells shall be equal to or greater than that required for a lintel of the same depth and loading condition that has an allowable clear span that is equal to or greater than that of the lintel without stirrups.
See Page 7-7 for additional notes.

~ Back to Top ~

Table 7.8. Maximum Allowable Clear Spans for 8-inch Nominal Thick Flat Lintels in Load-Bearing Walls1,2,3,4,5,6,13 Roof Clear Span 32 feet and Floor Clear Span 24 feet

Lintel Depth7, D(in.) Number of bars and bar size in top and bottom of lintel Steel yield strength8, fy(psi) Loading condition determined from Table 7.2
1 2 3 4 5
Maximum ground snow load (psf)
30 70 30 70 30 70 30 70
Maximum clear span of lintel (ft–inches)
8 Span without stirrups9,10 6-2 7-1 4-7 4-10 4-1 3-2 2-10 2-3 2-2
1 – #4 40,000 4-10 5-3 4-0 4-2 3-9 3-1 2-11 2-4 2-4
60,000 6-9 7-4 5-7 5-10 5-3 4-4 4-1 3-4 3-3
1 – #5 40,000 6-11 7-6 5-9 5-11 5-4 4-5 4-2 3-4 3-3
60,000 8-4 9-0 6-10 7-2 6-5 5-4 5-0 4-1 4-0
2 – #4
1 – #6
40,000 7-9 8-4 6-5 6-8 5-11 4-11 4-8 3-9 3-8
60,000 9-3 10-0 7-8 8-0 7-1 5-11 5-7 4-6 4-5
2 – #5 40,000 9-5 10-2 7-9 8-1 7-3 6-0 5-8 4-7 4-6
60,000 DR DR DR DR DR DR DR DR DR
Center distance A11,12 2-7 3-0 1-9 1-11 1-6 1-1 0-11 0-7 0-7
12 Span without stirrups9,10 5-6 6-7 4-7 4-10 4-2 3-5 3-3 2-8 2-8
1 – #4 40,000 6-0 6-9 5-2 5-5 4-10 4-0 3-9 3-1 3-0
60,000 7-3 8-2 6-4 6-7 5-10 4-11 4-7 3-9 3-8
1 – #5 40,000 7-5 8-4 6-5 6-8 6-0 5-0 4-8 3-10 3-9
60,000 10-4 11-8 9-0 9-4 8-4 7-0 6-6 5-4 5-3
2 – #4
1 – #6
40,000 9-7 10-10 8-4 8-8 7-9 6-6 6-1 4-11 4-10
60,000 11-7 13-1 10-1 10-6 9-4 7-10 7-4 6-0 5-10
2 – #5 40,000 11-10 13-4 10-3 10-8 9-6 8-0 7-6 6-1 5-11
60,000 14-2 15-11 12-3 12-9 11-5 9-7 8-11 7-3 7-1
2 – #6 40,000 13-11 15-8 12-1 12-7 11-3 9-4 8-5 6-2 5-11
60,000 DR DR DR DR DR DR DR DR DR
Center distance A11,12 3-10 4-11 2-11 3-2 2-6 1-9 1-6 1-0 1-0
16 Span without stirrups9,10 7-3 8-11 6-4 6-8 5-9 4-9 4-6 3-9 3-8
1 – #4 40,000 6-9 7-10 6-1 6-4 5-8 4-9 4-5 3-8 3-7
60,000 8-3 9-7 7-5 7-9 6-11 5-10 5-5 4-5 4-4
1 – #5 40,000 8-5 9-9 7-7 7-11 7-1 5-11 5-7 4-6 4-5
60,000 10-3 11-11 9-3 9-7 8-7 7-3 6-9 5-6 5-5
2 – #4
1 – #6
40,000 9-6 11-0 8-7 8-11 8-0 6-8 6-3 5-1 5-0
60,000 13-2 15-5 11-11 12-5 11-1 9-4 8-9 7-1 7-0
2 – #5 40,000 13-6 15-8 12-2 12-8 11-4 9-6 8-11 7-3 7-1
60,000 16-3 18-11 14-8 15-3 13-8 11-5 10-9 8-9 8-6
2 – #6 40,000 15-11 18-7 14-5 15-0 13-5 11-3 10-3 7-7 7-4
60.000 19-1 22-0 17-3 17-11 16-1 13-4 12-0 8-9 8-6
Center distance A11,12 4-11 6-7 4-0 4-4 3-6 2-5 2-2 1-5 1-4
20 Span without stirrups9,10 8-9 11-3 8-0 8-5 7-4 6-1 5-9 4-10 4-9
1 – #5 40,000 9-1 10-11 8-6 8-10 8-0 6-8 6-3 5-1 5-0
60,000 11-1 13-4 10-5 10-10 9-9 8-2 7-8 6-3 6-1
2 – #4
1 – #6
40,000 10-3 12-4 9-8 10-0 9-0 7-6 7-1 5-9 5-8
60,000 12-6 15-0 11-9 12-2 10-11 9-2 8-7 7-1 6-11
2 – #5 40,000 12-9 15-4 12-0 12-5 11-2 9-4 8-10 7-2 7-0
60,000 17-9 21-4 16-8 17-3 15-6 13-0 12-3 10-0 9-9
2 – #6 40,000 17-5 20-11 16-4 17-0 15-3 12-9 12-0 9-0 8-9
60,000 21-0 25-3 19-8 20-5 18-4 15-3 13-10 10-3 9-11
Center distance A11,12 5-9 8-3 5-0 5-5 4-4 3-1 2-9 1-10 1-9
24 Span without stirrups9,10 10-1 13-5 9-8 10-2 8-11 7-5 6-11 5-10 5-9
1 – #5 40,000 9-8 11-11 9-4 9-9 8-9 7-4 6-11 5-8 5-6
60,000 11-9 14-7 11-5 11-10 10-8 9-0 8-5 6-11 6-9
2 – #4
1 – #6
40,000 10-11 13-6 10-7 11-0 9-10 8-4 7-10 6-5 6-3
60,000 13-4 16-5 12-11 13-5 12-0 10-2 9-6 7-9 7-7
2 – #5 40,000 13-7 16-9 13-2 13-8 12-3 10-4 9-8 7-11 7-9
60,000 18-11 23-4 18-4 19-0 17-2 14-5 13-6 11-1 10-10
2 – #6 40,000 18-7 22-11 18-0 18-8 16-10 14-2 13-3 10-6 10-2
60,000 22-5 27-8 21-9 22-7 20-4 17-1 15-8 11-8 11-4
Center distance A11,12 6-5 9-9 6-0 6-6 5-3 3-9 3-3 2-2 2-1
For SI: 1 inch = 25.4 mm; 1 psf = 0.0479 kN/m2; 1 ft = 0.3048 m; Grade 40 = 280 MPa; Grade 60 = 420 MPa
7-12 Top and bottom reinforcement for lintels without stirrups shown in shaded cells shall be equal to or greater than that required for a lintel of the same depth and loading condition that has an allowable clear span that is equal to or greater than that of the lintel without stirrups.
See Page 7-7 for additional notes.

Table 7.9. Maximum Allowable Clear Spans for 10-inch Nominal Thick Flat Lintels in Load-Bearing Walls1,2,3,4,5,6,13 Roof Clear Span 40 feet and Floor Clear Span 32 feet

Lintel Depth7, D(in.) Number of bars and bar size in top and bottom of lintel Steel yields trength8, fy(psi) Loading condition determined from Table 7.2
1 2 3 4 5
Maximum ground snow load (psf)
30 70 30 70 30 70 30 70
Maximum clear span of lintel (ft–inches)
8 Span without stirrups9,10 6-0 7-2 4-7 4-10 4-1 3-1 2-11 2-3 2-2
1 – #4 40,000 4-3 4-9 3-7 3-9 3-4 2-9 2-7 2-1 2-1
60,000 5-11 6-7 5-0 5-3 4-8 3-10 3-8 2-11 2-11
1 – #5 40,000 6-1 6-9 5-2 5-4 4-9 3-11 3-9 3-0 2-11
60,000 7-4 8-1 6-3 6-5 5-9 4-9 4-6 3-7 3-7
2 – #4
1 – #6
40,000 6-10 7-6 5-9 6-0 5-5 4-5 4-2 3-4 3-4
60,000 8-2 9-1 6-11 7-2 6-6 5-4 5-0 4-1 4-0
2 – #5 40,000 8-4 9-3 7-1 7-4 6-7 5-5 5-1 4-1 4-0
60,000 9-11 11-0 8-5 8-9 7-10 6-6 6-1 4-8 4-6
2 – #6 40,000 9-9 10-10 8-3 8-7 7-9 6-4 5-10 4-1 4-0
60,000 DR DR DR DR DR DR DR DR DR
Center distance A11,12 2-6 3-1 1-10 1-11 1-7 1-1 0-11 0-7 0-7
12 Span without stirrups9,10 5-5 6-7 4-7 4-10 4-3 3-5 3-3 2-8 2-8
1 – #4 40,000 5-3 6-0 4-8 4-10 4-4 3-7 3-4 2-9 2-8
60,000 6-5 7-4 5-8 5-10 5-3 4-4 4-1 3-4 3-3
1 – #5 40,000 6-6 7-6 5-9 6-0 5-5 4-5 4-2 3-5 3-4
60,000 7-11 9-1 7-0 7-3 6-7 5-5 5-1 4-2 4-0
2 – #4
1 – #6
40,000 7-4 8-5 6-6 6-9 6-1 5-0 4-9 3-10 3-9
60,000 10-3 11-9 9-1 9-5 8-6 7-0 6-7 5-4 5-3
2 – #5 40,000 10-5 12-0 9-3 9-7 8-8 7-2 6-9 5-5 5-4
60,000 12-7 14-5 11-2 11-6 10-5 8-7 8-1 6-6 6-4
2 – #6 40,000 12-4 14-2 10-11 11-4 10-2 8-5 7-8 5-7 5-5
60,000 14-9 17-0 13-1 13-6 12-2 10-0 9-1 6-6 6-4
Center distance A11,12 3-9 4-11 2-11 3-2 2-7 1-9 1-7 1-0 1-0
16 Span without stirrups9,10 7-1 9-0 6-4 6-8 5-10 4-9 4-6 3-9 3-8
1 – #4 40,000 5-11 7-0 5-5 5-8 5-1 4-3 4-0 3-3 3-2
60,000 7-3 8-7 6-8 6-11 6-3 5-2 4-10 3-11 3-10
1 – #5 40,000 7-4 8-9 6-9 7-0 6-4 5-3 4-11 4-0 3-11
60,000 9-0 10-8 8-3 8-7 7-9 6-5 6-0 4-11 4-9
2 – #4
1 – #6
40,000 8-4 9-11 7-8 7-11 7-2 5-11 5-7 4-6 4-5
60,000 10-2 12-0 9-4 9-8 8-9 7-3 6-10 5-6 5-5
2 – #5 40,000 10-4 12-3 9-6 9-10 8-11 7-4 6-11 5-8 5-6
60,000 14-4 17-1 13-3 13-8 12-4 10-3 9-8 7-10 7-8
2 – #6 40,000 14-1 16-9 13-0 13-5 12-2 10-1 9-6 7-0 6-10
60.000 17-0 20-2 15-8 16-2 14-7 12-0 10-11 8-0 7-9
Center distance A11,12 4-9 6-8 4-0 4-4 3-6 2-5 2-2 1-5 1-4
20 Span without stirrups9,10 8-7 11-4 8-1 8-5 7-5 6-1 5-9 4-10 4-9
1 – #4 40,000 6-5 7-10 6-2 6-4 5-9 4-9 4-6 3-8 3-7
60,000 7-10 9-7 7-6 7-9 7-0 5-10 5-6 4-5 4-4
1 – #5 40,000 8-0 9-9 7-8 7-11 7-2 5-11 5-7 4-6 4-5
60,000 9-9 11-11 9-4 9-8 8-9 7-3 6-10 5-6 5-5
2 – #4
1 – #6
40,000 9-0 11-1 8-8 8-11 8-1 6-9 6-4 5-2 5-0
60,000 11-0 13-6 10-6 10-11 9-10 8-2 7-9 6-3 6-2
2 – #5 40,000 11-3 13-9 10-9 11-1 10-0 8-4 7-10 6-5 6-3
60,000 15-8 19-2 15-0 15-6 14-0 11-8 11-0 8-11 8-9
2 – #6 40,000 15-5 18-10 14-8 15-2 13-9 11-5 10-9 8-6 8-3
60,000 18-7 22-9 17-9 18-5 16-7 13-10 12-9 9-5 9-2
Center distance A11,12 5-7 8-4 5-1 5-5 4-5 3-1 2-9 1-10 1-9
24 Span without stirrups9,10 9-11 13-7 9-9 10-2 9-0 7-5 7-0 5-10 5-9
1 – #5 40,000 8-6 10-8 8-5 8-8 7-10 6-6 6-2 5-0 4-11
60,000 10-5 13-0 10-3 10-7 9-7 8-0 7-6 6-1 6-0
2 – #4
1 – #6
40,000 9-7 12-1 9-6 9-9 8-10 7-5 7-0 5-8 5-6
60,000 11-9 14-9 11-7 11-11 10-10 9-0 8-6 6-11 6-9
2 – #5 40,000 12-0 15-0 11-9 12-2 11-0 9-2 8-8 7-1 6-11
60,000 14-7 18-3 14-4 14-10 13-5 11-2 10-7 8-7 8-5
2 – #6 40,000 14-3 17-11 14-1 14-7 13-2 11-0 10-4 8-5 8-3
60,000 19-11 25-0 19-7 20-3 18-4 15-3 14-5 10-10 10-7
Center distance A11,12 6-3 9-11 6-1 6-6 5-4 3-9 3-4 2-2 2-1
For SI: 1 inch = 25.4 mm; 1 psf = 0.0479 kN/m2; 1 ft = 0.3048 m; Grade 40 = 280 MPa; Grade 60 = 420 MPa
7-13 Top and bottom reinforcement for lintels without stirrups shown in shaded cells shall be equal to or greater than that required for a lintel of the same depth and loading condition that has an allowable clear span that is equal to or greater than that of the lintel without stirrups.
See Page 7-7 for additional notes.

~ Back to Top ~

Table 7.10. Maximum Allowable Clear Spans for 10-inch Nominal Thick Flat Lintels in Load-Bearing Walls1,2,3,4,5,6,13 Roof Clear Span 32 feet and Floor Clear Span 24 feet

Lintel Depth7, D(in.) Number of bars and bar size in top and bottom of lintel Steel yield strength8, fy(psi) Loading condition determined from Table 7.2
1 2 3 4 5
Maximum ground snow load (psf)
30 70 30 70 30 70 30 70
Maximum clear span of lintel (ft–inches)
8 Span without stirrups9,10 7-2 8-6 5-5 5-10 4-10 3-5 3-2 2-5 2-4
1 – #4 40,000 4-9 5-3 4-0 4-2 3-9 3-0 2-10 2-3 2-2
60,000 6-7 7-4 5-7 5-10 5-3 4-2 3-11 3-2 3-1
1 – #5 40,000 6-9 7-5 5-9 5-11 5-4 4-3 4-0 3-2 3-2
60,000 8-2 9-0 6-11 7-2 6-5 5-1 4-10 3-10 3-9
2 – #4
1 – #6
40,000 7-7 8-4 6-5 6-8 6-0 4-9 4-6 3-7 3-6
60,000 9-2 10-1 7-9 8-0 7-2 5-9 5-5 4-4 4-3
2 – #5 40,000 9-3 10-3 7-10 8-2 7-4 5-10 5-6 4-5 4-4
60,000 11-1 12-2 9-4 9-9 8-9 6-11 6-6 5-2 5-0
2 – #6 40,000 10-10 12-0 9-3 9-7 8-7 6-10 6-5 4-7 4-5
60,000 DR DR DR DR DR DR DR DR DR
Center distance A11,12 3-1 3-9 2-3 2-5 1-11 1-3 1-1 0-8 0-8
12 Span without stirrups9,10 6-2 7-8 5-3 5-7 4-10 3-8 3-5 2-10 2-9
1 – #4 40,000 5-9 6-8 5-2 5-4 4-10 3-10 3-7 2-11 2-10
60,000 7-0 8-1 6-3 6-6 5-10 4-8 4-5 3-6 3-6
1 – #5 40,000 7-2 8-3 6-5 6-8 6-0 4-9 4-6 3-7 3-6
60,000 8-9 10-1 7-10 8-1 7-3 5-10 5-6 4-5 4-4
2 – #4
1 – #6
40,000 8-1 9-4 7-3 7-6 6-9 5-4 5-1 4-1 4-0
60,000 11-3 13-0 10-1 10-6 9-5 7-6 7-1 5-8 5-7
2 – #5 40,000 11-6 13-3 10-3 10-8 9-7 7-7 7-2 5-9 5-8
60,000 13-10 16-0 12-4 12-10 11-6 9-2 8-8 7-0 6-10
2 – #6 40,000 13-7 15-8 12-2 12-7 11-4 9-0 8-6 6-1 5-11
60,000 16-3 18-6 14-6 15-1 13-6 10-9 10-2 7-2 7-0
Center distance A11,12 4-6 6-0 3-7 3-11 3-2 2-0 1-9 1-2 1-1
16 Span without stirrups9,10 8-0 10-5 7-3 7-8 6-8 5-1 4-9 3-11 3-10
1 – #4 40,000 6-5 7-9 6-0 6-3 5-8 4-6 4-3 3-5 3-4
60,000 7-10 9-5 7-4 7-8 6-11 5-6 5-2 4-2 4-1
1 – #5 40,000 8-0 9-8 7-6 7-10 7-0 5-7 5-4 4-3 4-2
60,000 9-9 11-9 9-2 9-6 8-7 6-10 6-6 5-3 5-1
2 – #4
1 – #6
40,000 9-1 10-10 8-6 8-10 7-11 6-4 6-0 4-10 4-9
60,000 11-0 13-3 10-4 10-9 9-8 7-9 7-3 5-10 5-9
2 – #5 40,000 11-3 13-6 10-7 10-11 9-10 7-11 7-5 6-0 5-11
60,000 15-8 18-9 14-8 15-3 13-8 10-11 10-4 8-4 8-2
2 – #6 40,000 15-4 18-5 14-5 14-11 13-5 10-9 10-2 7-8 7-6
60,000 18-6 22-2 17-4 18-0 16-2 12-11 12-2 8-9 8-6
Center distance A11,12 5-7 8-1 4-11 5-4 4-4 2-9 2-5 1-7 1-6
20 Span without stirrups9,10 9-6 13-0 9-3 9-8 8-5 6-6 6-1 5-0 5-0
1 – #4 40,000 6-11 8-7 6-9 7-0 6-4 5-1 4-10 3-11 3-10
60,000 8-6 10-3 8-3 8-7 7-9 6-3 5-10 4-9 4-8
1 – #5 40,000 8-8 10-9 8-5 8-9 7-11 6-4 6-0 4-10 4-9
60,000 10-7 13-1 10-4 10-8 9-8 7-9 7-4 5-11 5-9
2 – #4
1 – #6
40,000 9-9 12-2 9-6 9-11 8-11 7-2 6-9 5-6 5-4
60,000 11-11 14-9 11-8 12-1 10-10 8-9 8-3 6-8 6-6
2 – #5 40,000 12-2 15-1 11-10 12-4 11-1 8-11 8-5 6-9 6-8
60,000 16-11 21-1 16-7 17-2 15-6 12-5 11-9 9-6 9-4
2 – #6 40,000 16-7 20-8 16-3 16-10 15-2 12-2 11-6 9-3 9-0
60,000 20-1 25-0 19-8 20-4 18-4 14-9 13-11 10-3 10-0
Center distance A11,12 6-6 10-0 6-3 6-8 5-5 3-6 3-1 2-0 2-0
24 Span without stirrups9,10 10-11 15-6 11-1 11-8 10-2 7-11 7-5 6-2 6-0
1 – #5 40,000 9-1 11-8 9-3 9-7 8-8 7-0 6-7 5-4 5-3
60,000 11-2 14-3 11-3 11-8 10-7 8-6 8-0 6-6 6-5
2 – #4
1 – #6
40,000 10-4 13-2 10-5 10-10 9-9 7-10 7-5 6-0 5-11
60,000 12-7 16-1 12-9 13-3 11-11 9-7 9-1 7-4 7-3
2 – #5 40,000 12-10 16-5 13-0 13-6 12-2 9-10 9-3 7-6 7-4
60,000 15-8 20-0 15-10 16-5 14-10 11-11 11-3 9-2 9-0
2 – #6 40,000 15-4 19-7 15-6 16-1 14-6 11-9 11-1 9-0 8-9
60,000 21-4 27-4 21-7 22-5 20-3 16-4 15-5 11-10 11-6
Center distance A11,12 7-3 11-10 7-5 8-0 6-6 4-3 3-9 2-6 2-5
For SI: 1 inch = 25.4 mm; 1 psf = 0.0479 kN/m2; 1 ft = 0.3048 m; Grade 40 = 280 MPa; Grade 60 = 420 MP
7-14 Top and bottom reinforcement for lintels without stirrups shown in shaded cells shall be equal to or greater than that required for a lintel of the same depth and loading condition that has an allowable clear span that is equal to or stirrups. See Page 7-7 for additional notes.

Table 7.17. Maximum Allowable Clear Spans for Flat Lintels Without Stirrups in Non-Load-Bearing Walls 1,2,3,4,5,7,8

Lintel Depth6, D(in.) Number of bars and bar size Steel yield strength, fy(psi) Nominal Wall Thickness (inches)
4 6